NEMA PREMIUM EFFICIENCY ODP – COMMERCIAL DUTY
SDP0606C
60 HP
230/460 Voltage
1200 RPM
404TC Frame
3 – Phase
Amps at 230: 139.06
Amps at 460: 69.53
Enclosure – ODP
Efficiency 94.5
Drive End Bearing – 6317
Non-Drive End Bearing – 6317
Open Drip Proof IP22 Design
60 Hz, 230/460V or 575V
Horizontal F1 Mount
3600, 1800 & 1200 RPM
NEMA Premium Efficiency
1.15 S.F. Sine Wave Power; 1.0 S.F. VFD Power
Class F Insulation
Class B Temperature Rise
Max Elevation 3300ft
Continuous Duty
40C Ambient
Shielded Bearings Frames 140T-280T and Open Bearings with Regreaseable Provisions Frames 280TS, 320T and Larger
Polyrex EM Grease in all Regreaseable Bearings, Multemp SRL Grease in Shielded Bearings
Aluminum Rotor
Cast-Iron Frame and End Brackets
Rolled Steel Conduit Box up to 400T Frames; Fabricated Steel Conduit Box 440T Frames and Larger
Number of Leads 230/460V: 9 Leads 1-5HP; 12 Leads 7.5-125HP; 6 Leads 150 and Above
Number of Leads 575V: 3 Leads up to 449T; 6 Leads 5000 Frames and Larger
Solderless Lug Terminals on All Leads
Grounding Terminal Inside Main Terminal Box
Interchangeable F1 and F2 mounting up to 449T
Paint System: Phenolic Rust Proof Base with Lacquer Top Coat
Stainless Steel Nameplate
Rubber Flinger on DE up to 280T; Steel Flinger on DE 280TS and Larger
*HPE High Pulse Endurance Spike Resistant Wire
Phenolic Alkyd Resin Varnish 140T to 400T Frames; 2 Dips Phenolic Alkyd Resin Varnish and 1 Coat Spray Enamel 440T Frames and Larger
Usable on 208V Sinusoidal Power Only
Winding RTDs, Space Heaters and Provisions for Bearing RTDs Standard 5000 Frames and Larger
CSA Certified, UL Recognized and CE Marked
UL Listed (UL 1004-5) for Fire Pump Applications (1-400HP)
CSA Energy Efficiency Verification (EEV)
*Meets NEMA MG1 Part 31.4.4.2
*Speed Ranges up to 10:1 CT, and 20:1 VT. Refer to data sheet for rating specific turn down ratios